INTRODUCTION

The BTRP230 thermostat from Salus Controls is a stylish and accurate programmable flush-mount digital room thermostat for Bezel 55. You can now simply adjust your home temperature as desired in order to create a comfortable home environment.

PRODUCT COMPLIANCE

This product complies with the essential requirements of the following EC Directives: 2014/30/EU, 2014/35/EU and 2011/65/EU. The full text of the EU Declaration of Conformity is available at the following internet address: www.saluslegal.com.

SALUS BTRP230 Pure White Room Thermostat UP Electronic Digital User Guide - Warning or Caution iconSAFETY INFORMATION

Use in accordance with the regulations. Indoor use only. Keep your equipment completely dry. Disconnect your equipment before cleaning it with a dry towel. The unit is to be used for the control of room temperature inside the house.

INSTALLATION

This accessory must be fitted by a competent person, and installation must comply with the guidance, standards, and regulations applicable to the city, country or state where the product is installed. Failure to comply with the relevant standards could lead to prosecution.

Box Content

  • Front caseSALUS-BTRP230(20)-Thermostat-fig.1
  • Rear case
  • Quick guideSALUS-BTRP230(20)-Thermostat-fig.2
  • 2x fixing screws

Wiring

You can wire the thermostat directly to the KL08NSB wiring centre or to an actuator (purchased separately).

SALUS-BTRP230(20)-Thermostat-fig.3 SALUS-BTRP230(20)-Thermostat-fig.4

Mounting

Please refer to the images below for mounting your thermostat.

SALUS-BTRP230(20)-Thermostat-fig.5

Terminals

SALUS-BTRP230(20)-Thermostat-fig.6

BTR230 Jumpers

SALUS-BTRP230(20)-Thermostat-fig.7

Different features of the BTR230 can be switched ON or OFF with the jumpers.
In order to do this please follow the table below.SALUS-BTRP230(20)-Thermostat-fig.8

The jumpers from 1 to 5 are representing the number of actuators that you can connect to the thermostat.
After the actuators are mounted please move the jumper on the correct number (the same as the number of actuators).

Night Setback

NSB (Night SetBack) Function

NSB Mode is always ON, giving the possibility to choose a reduction between 2°C or 4°C. The NSB signal is activated every 1 second. When the signal is received the setpoint temperature will be reduced by 2°C or 4°C.

Heating and Cooling

Heating and Cooling Selection

The Heating/Cooling function is determined by the CO terminal connection.

  • CO 0 V = Heat mode
  • CO 230V= Cool mode

Cooling Blocked

The cooling Blocked function

  • Cooling Enabled: Set the jumper to the ON positionSALUS-BTRP230(20)-Thermostat-fig.9. The thermostat will run in normal cooling mode. That means that it will open/close the actuators when necessary. The LED will be BLUE when the cooling function is running.
  • Cooling Disabled: Set the jumper to the OFF positionSALUS-BTRP230(20)-Thermostat-fig.10. CO terminal will be deactivated. Heat mode only.

Control Patterns

This product has a jumper to choose output control pattern, PWM output or ON/OFF output.
In heating mode, there is PWM or ON/OFF control output. In cooling mode, only ON/OFF control output.

SALUS Controls plc
SALUS House  Dodworth Business Park South, Whinby Road, Dodworth, Barnsley S75 3SP UK.
SALES: T: +44 (0) 1226 323961
E: [email protected]
TECHNICAL: T: +44 (0) 1226 323961
E: [email protected]
Issue Date: Feb 2014
Maintaining a policy of continued product development SALUS Controls plc reserves the right to change the specification, design, and materials of products listed in this brochure without prior notice. SALUS Controls is a member of the Computime Group 00089.

REFERENCE

Download Manual:

SALUS BTRP230(20) Thermostat Quick Guide

Other manuals:

SALUS BTRP230(20) Thermostat Wiring Diagram

Salus-logo

SALUS BTRP230(20) Thermostat Quick Guide


Posted

in

by

Comments

Leave a Reply

Your email address will not be published. Required fields are marked *

To respond on your own website, enter the URL of your response which should contain a link to this post’s permalink URL. Your response will then appear (possibly after moderation) on this page. Want to update or remove your response? Update or delete your post and re-enter your post’s URL again. (Find out more about Webmentions.)