Oventrop EC010927 Digital Room Thermostat
General information
Information regarding installation and operating instructions
These installation and operating instructions serve the installer to install the room thermostat professionally and to set it into operation.
Other valid documents:
Manuals of all system components, regulations for prevention of accidents as well as rules of technology.
Keeping of documents
These installation and operating instructions should be kept by the user of the system
Symbol explanation
Safety guidelines are displayed by symbols. These guidelines are to be observed to prevent accidents, damage to property and malfunctions.
DANGER!
Imminent danger to life and limb!
Attention!
Potential dangerous situation for product, system or environment!
Note!
Useful information and notes!
Copyright
The installation and operating instructions are copyrighted.
Safety notes
Correct use
- Operating safety is only guaranteed if the room thermostat is used correctly.
- The digital room thermostat is used for room temperature control.
- Any use of the room thermostat outside the above circumstances will be considered as non-compliant and misused.
- Claims of any kind against the manufacturer and/or its authorized representatives due to damages caused by incorrect use cannot be accepted.
- The observance of the operating and installation instructions is part of the compliance terms.
Transport, packaging and storage
Transport inspection
Upon receipt, check delivery for any damages caused during transit. Any damages must be reported immediately upon receipt.
Storage
The room thermostat must only be stored under the following conditions:
· Do not store in open air, keep dry and free from dust.
· Do not expose to aggressive fluids or heat sources.
· Protect from direct sunlight and mechanical agitation.
· Storage temperature: 0 up to 40°C, max. relative humidity of air: 95 %
Packaging
All packaging material must be disposed of environmentally friendly
Technical data
Performance data
- Temperature setting range: 5 to 35°C
- Switching temperature difference: about ±1K
- Operating voltage: – Item no. 1152561:
- 100-230 V AC, 50/60Hz
- Item no. 1152562:
- 24 V AC, 50/60Hz
- Switching capacity: – Item no. 1152561:
- 2 (1) A; 230 V AC
- – Item no. 1152562:
- 2 (1) A; 24 V AC
- Power: < 2W
- Fuse: 2 A, 250 V
- Protection: IP 30
Dimensions / Connection dimensions
Construction and function
Summary / Functional description
The digital room thermostat is used for room temperature control in self-contained rooms. The room temperature is controlled via a valve which is activated through an actuator. When the room temperature has reached the nominal value, the valve will be closed. Setting of the nominal value by key stroke, visualisation on a large LCD display with blue backlighting. The backlighting is active when pressing the keys. Settings can be stored.
Application range
The digital room thermostat can be used in combination with the Oventrop two point actuators (M 30 x 1.5) for individual room temperature control
Installation
Extent of supply
Before installing the room thermostat, please check delivery for completeness and any damages caused during transit.
Switch off current supply
Open casing by pushing back the snap hooks at the lower side with a 3.5 mm screwdriver. Carry out wiring according to the wiring diagram (Illustr. 6.2). Now fix casing with the help of the enclosed screws (Illustr. 6.1) and close it again
The installation location of the room thermostat must comply with the following conditions:
- The room thermostat must not be exposed to a direct heat source (e.g. sunlight) or cold source.
- A good air circulation must be guaranteed.
- The room thermostat must be easily accessible.
Operation
The display shows the current room temperature (RT) at the installation location. The current time and day of the week, the symbol as well as the set operating mode are also displayed.
Switching the thermostat off/on
The thermostat and display are switched off by pressing the key. The thermostat is switched on again by pressing the key
once more.
Frost protection mode
To activate the frost protection, switch the thermostat off by pressing the key
Now keep the key M pressed for about 3 seconds. “00“ (inactivated) appears on the display. Now choose “01“ (activated) by pressing the key
The symbol appears if the frost protection mode is activated and the room thermostat is switched off. If the room temperature drops below 5°C, the thermostat is switched on automatically. The room temperature is now increased to 7°C. Having reached this value, the thermostat is switched off again automatically.
Temperature calibration
Temperature calibration must only be carried out if the indicated temperature is not correct. Switch off the room thermostat by using the key. Now press the keys
simultaneously for about 3 seconds. The room temperature which visualises on the display is adapted with the help of the keys
The calibration settings are stored by pressing the key
Normal operating mode
- RT: Thermostat in operating mode; the display indicates “RT“ and the current room temperature.
- SET: By pressing the key
once, the display indicates “SET“ and the set nominal temperature.
- The nominal temperature can be increased or reduced with the help of the keys
- This temperature modification is only active until the next programmed temperature.
- The symbol is displayed during active temperature control and during heating or cooling.
Modification of the operating mode
The operating mode can be chosen by pressing the key for 3 seconds (thermostat is switched on).
- 01 = Constant operation
- 02 = Timer On/Off; the display indicates the symbol
- 03 = Programming; the display indicates the symbol
Setting the time and the day of the week
Press the key. Now set the hours with the help of the keys
press
to set the minutes. Now press
again and set the day of the week.
Setting of the timer
If the operating mode “TIMER ON/OFF“ and the symbol appears, the timer can be switched on and off. Press the key
until “TIMER ON“ and “hh“appear. The hours can be set with the help of the keys
. If the key
is pressed again, the minutes can be set using the keys
. Now press the key
. “TIMER OFF“ and “hh“are indicated. The hours can be set by pressing the keys
. If the key
is pressed again, the minutes can be set with the help of the keys
. Having defined “TIMER OFF“, settings are completed.
There are two ways to switch off the operating mode:
- Chose the mode “Constant operation“ or “Programming“
- Set “TIMER ON/OFF“ to “00:00“ in the switching mode
Setting of the weekly program
- If the operating mode “Programming“ has been chosen and the symbol
appears, the temperature programmes can be set.
- Setting of the nominal temperature for the days of the week (Mo-Fr) and the weekend (Sa-Su) are autonomous. 4 time intervals per day can be set.
- Press the key
for about 3 seconds. The display now indicates 1 and “Mo. Tu. We. Th. Fr.“
- The first time interval for the days of the week can now be set.
- Use the keys
to set the required start-up time and confirm it by pressing the key
- Set the required temperature using the keys
confirm it by pressing the key
Repeat this procedure for the time intervals 2-4 of the days of the week.
- Now the settings for the weekend (the display shows “Su. Sa.“) can be carried out the same way.
- Chose the mode “Constant operating“ or “TIMER ON/OFF” to switch off the operating mode.
Example
Room temperature for the days of the week shall be set as follows.
Temperature sequence: Required setting:
- 05:30 – 08:00 h 22°C Number 1: 05:30; 22°C
- 08:00 – 14:00 h 18°C Number 2: 08:00; 18°C
- 14:00 – 23:00 h 23°C Number 3: 14:00; 23°C
- 23:00 – 05:30 h 19°C Number 4: 23:00; 19°C
Maintenance
The room thermostat must only be cleaned with mild detergent. Detergents must not penetrate the room thermostat, they must not be sprayed onto the thermostat but onto a cleaning cloth.
General terms and conditions of sale and delivery
Oventrops general terms and conditions of sale and delivery valid at the time of supply are applicable.
REFERENCE
DOWNLOAD MANUALS:
Oventrop EC010927 Digital Room Thermostat User Manuals
OTHER MANUALS:
Oventrop EC010927 Digital Room Thermostat Technical information