ESBEE LOGO

ESBE TPH114 Digital Room Thermostats  

ESBE- TPH114- Digital- Room-Thermostats -pro

INSTALLATION

WARNING

QUICK GUIDE FOR SETTING THE TIME SCHEDULE

GENERALITIES

This device is a battery powered weekly digital programmable thermo-hygrostat for the control of room temperature and relative humidity on three levels: Comfort, Economy or Off / Antifreeze. The device can be used in heating and cooling plants. The programmable thermo-hygrostat has a large backlit LCD display for all functional indications, the program schedule set, the room temperature reading, the relative humidity reading, or, as desired, the actual time. Allows to set up to 7 different programs, one for each day of the week, with a minimum intervention time of 1/2 hour over 24 hours. In addition, the device offers the possibility of setting the Antifreeze temperature value, dew point control and sensor Offset value adjustment.

DESCRIPTION OF CONTROLS

LEGEND

DISPLAY SYMBOLS

In the following is explained the meaning of some symbols which may appear on the displayESBE- TPH114- Digital- Room-Thermostats-fig- (15)

STARTING UP
When starting up for the first time:

Setting the current time and day
To set the clock of the programmable thermo-hygrostat carry out the following steps

Time/Temperature/Humidity Display
By repeatedly pressing the ‘ESBE- TPH114- Digital- Room-Thermostats-fig- (14)‘ the display can alternately show the actual time, the room temperature (in °C) read by the internal sensor, distinguished by the ‘ESBE- TPH114- Digital- Room-Thermostats-fig- (15) ‘ icon, the room temperature (in °C) read by the remote probe (if connected) distinguished by the ‘ESBE- TPH114- Digital- Room-Thermostats-fig- (16) ‘ icon and the room humidity (in %RH) read by the internal sensor, distinguished by the ‘ ESBE- TPH114- Digital- Room-Thermostats-fig- (15)‘ icon. The temperature and humidity readings are displayed corrected by the Offset value set.

ATTENTION: In order to optimise battery duration, the programmable thermo-hygrostat performs sensor readings and error controls every 3 minutes or when ‘Ok’ is pressed and consequently, decides on activation or deactivation of the relay. Any error message must disappear within 3 minutes or on pressing the ‘Ok’ key. If the message does not disappear then problems have been detected on the sensors.

Note:
If the ‘ rEG ’ parameter is set at ‘ In ‘, but an error is detected on the internal sensor, the display will show ‘ SEnS E xx ’. In this situation the adjustment will be automatically interrupted and both relays will be placed in the Normally Open position. If the ‘ rEG ’ parameter has been set at ‘ Out ‘ but the remote probe has not been connected or is damaged, the display will show the respective wording ‘ SEnS OPEN ‘ or ‘ SEnS SHrt ‘ with the ‘ ‘ icon on.

Comfort and Economy temperatures/humidity adjustment
During normal operation, the display shows the room temperature and humidity reading and the icon relative to the current setting modeESBE- TPH114- Digital- Room-Thermostats-fig- (17) orESBE- TPH114- Digital- Room-Thermostats-fig- (18). The programmable thermo-hygrostat reads the room temperature from the internal or external sensor (depending on the setting made in the ‘ rEG ’ parameter), while the humidity is only read on the internal sensor. The flashing ‘ ESBE- TPH114- Digital- Room-Thermostats-fig- (15)‘ icon indicates that the adjustment (temperature or humidity) takes place on an internal sensor, while the flashing ‘ESBE- TPH114- Digital- Room-Thermostats-fig- (16)‘ icon indicates that the adjustment (temperature only) takes place on the remote probe. Activation of the relay that controls the room humidity management system is indicated on the display by switch-on of the ‘ESBE- TPH114- Digital- Room-Thermostats-fig- (19) ‘ icon. The activation of the relay that controls the room heating/cooling management system is indicated on the display by the switch-on of the ‘ESBE- TPH114- Digital- Room-Thermostats-fig- (20) ’ icon for heating and the ‘ ESBE- TPH114- Digital- Room-Thermostats-fig- (21)’ icon for cooling.

Proceed as follows to adjust:

Note: Normally, in order to have night -time adjustment, the economy temperature/humidity must have a value lower than the comfort value.

The programmable thermo-hygrostat will adjust the room temperature in comfort or economy mode in agreement with the hourly program set (see ‘ USER PARAMETER SETTING ‘ paragraph).

Dew point control
The dew point (managed in the user parameter ‘ C-dP ’), represents the temperature below which condensate forms on the surfaces and depends on the temperature and humidity present in the room.

ATTENTION

The table blow (table 1) shows the dew point value (expressed in °C), depending on the room temperature and relative humidity, expressed as ‘ %RH ’.

Table 1ESBE- TPH114- Digital- Room-Thermostats-fig- (22)

ATTENTION

For all details see ‘ ‘ C-dP ’ DEW POINT MANAGEMENT ‘.

Safety Control Algorithm

SETTING THE USER PARAMETERS
To enter the mode for setting the programmable thermo-hygrostat parameters, proceed as follows:

‘ PrOG ‘: SCHEDULE PROGRAMMING
Usually the circular band of dashes in the display shows the operating mode (Comfort, Economy, Off / antifrost) of the thermostat, while the vertical strip on the left shows the current day of the week
(1=Monday .. 7=Sunday) high lighted with a square around the number to which it relates programming.

To facilitate the programming operation it is sufficient to remember this rule:
ESBE- TPH114- Digital- Room-Thermostats-fig- (24)

To set the program schedule proceed as described below:

Note: You will exit the programming mode without memorizing the programmed schedule if more than 10 seconds elapse and you do not press any button; or else you can confirm the settings in sequence by pressing the ‘OK’ button without making any changes.

TIME INTERVALS PRESET

For every time interval (each dash corresponds to a half hour) set the operating mode by pressing one of the following buttons:

After programming the schedule for the entire week, press the ‘ OK ’ button. The programmable thermo-hygrostat will memorize the schedule set and the word ‘MEMO’ will appear on the display; the device will automatically exit the schedule programming mode.

WARNING

‘ AFr ’ ANTIFREEZE SETTING
The Antifreeze function allows you to select a minimum temperature to be maintained when the programmable thermo-hygrostat is off, so as to protect both the room and the equipment when the room temperature falls below the set value. The device leaves the factory with the Antifreeze function set on 3°C.

IMPORTANT: the function is active only when the device has been set in heating mode.

To set the Antifreeze temperature, carry out the following steps:

‘HYS’ SETTING THE HYSTERESIS
Setting this parameter allows to define the hysteresis, in °C, which is applied to the programmable thermo-hygrostat to adjust the room temperature, whenever the ‘ C-dP ‘ (dew point) user parameter has not been enabled.

To adjust the hysteresis perform the following steps:

‘ OPt ’ OPTIMIZATION SETTING
The optimization function consists in the option of turning on the heating or cooling earlier than the scheduled time in order to reach the set temperature by the scheduled time. The programmable thermo-hygrostat calculates the time necessary in order to reach the desired temperature and turns on the heating in advance accordingly, by the amount of time necessary to achieve the target.
The amount of time in advance may be 60 minutes at most and is calculated based on the average gradient of the previous 24 hours.

To set the optimization function carry out the following steps:

‘ OFS1 ’ INTERNAL SENSOR OFFSET SETTING
With this parameter it is possible to correct the temperature reading of the internal sensor by ±5°C in order to correct any systematic reading errors due to the positioning of the programmable thermohygrostat in areas unsuitable for measuring the room temperature. The device leaves the factory with the Offset set at 0.0°C.

To adjust the Offset value for the internal sensor, carry out the following steps:

OFS2 ’ REMOTE SENSOR OFFSET SETTING
With this parameter it is possible to correct the temperature reading of the remote sensor by ±5°C in order to correct any systematic reading errors due to the positioning of the remote sensor in areas unsuitable for measuring the room temperature. The device leaves the factory with the Offset set at 0.0°C.

To adjust the Offset value for the remote sensor, carry out the following steps:

‘ rEG ’ REGULATION SENSOR CHOICE SETTING
This parameter sets whether the room temperature regulation is made based on the programmable thermo-hygrostat internal sensor or the remote sensor connected to the connector ‘ B ‘ in Fig. 6.

For this parameter setting please find these directions:

WARNING: When the regulation is set according to the remote sensor ‘ Out ‘ and in case this sensor is missing or broken, the temperature regulation will be performed according to the internal sensor, even if the parameter remains set on ‘ Out ‘.

‘CLE’ SETTING CLEANING PROGRAM
This program is useful when the house is being cleaned and the windows are opened thus making both the heating and cooling of the premises unnecessary. In these conditions, the relays are blocked in Off for two hours.

Note:

‘HOL’ SET HOLIDAY PROGRAM
If you intend to be away for a relatively long period it is advisable to activate the Vacation Program, which will suspend the active operating mode for the desired number of hours (from 1 to 95) or days (from 1 to 99). At the end of the set number of hours or days, the programmable thermo-hygrostat will go back into the operating mode it was in prior to activation of the Vacation Program. While it is off, and in case the device has been set to Heating mode, the antifrost function will be in any case active, and the display will show the symbol ‘ESBE- TPH114- Digital- Room-Thermostats-fig- (27)‘ and the countdown of the time remaining to the end of the program.

Note: Access to the vacation program will NOT be enabled while the ‘ cleaning program ‘ is on.

To activate the vacation program proceed as follows:

‘H-C’ HEATING / COOLING SETTING
This setting is used to invert the operating logic of the thermostat relay according to whether a heating or air conditioning unit is being controlled.

ATTENTION:

To modify the operating logic, carry out the following procedure:

‘HYH’ SETTING HYGROSTAT HYSTERESIS
Setting this parameter allows to define the hysteresis, in %RH, which is applied to the programmable thermo-hygrostat to adjust the room humidity, whenever the ‘ C-dP ‘ (dew point) user parameter has not been enabled.

To adjust the differential, perform the following operations:

‘OFSH’ INTERNAL HUMIDITY SENSOR OFFSET SETTING
With this parameter it is possible to correct the humidity reading of the internal sensor by ±5%RH in order to correct any systematic reading errors due to the positioning of the programmable thermohygrostat in areas unsuitable for measuring the room humidity. The device leaves the factory with the Offset set at 0.0%RH.

To adjust the Offset value for the internal sensor, carry out the following steps:

‘dE-H’ DEHUMIDIFICATION/HUMIDIFICATION SETTING
This setting is used to invert the operating logic of the programmable thermo-hygrostat relay according to whether a dehumidification or humidification device is being controlled.

ATTENTION:

The procedure below must be followed to modify the operating logic:

‘C-dP’ DEW POINT MANAGEMENT
Using this parameter it is possible to enable/configure the Dew Point control in order to prevent the formation of surface condensate.

Proceed as follows to set this parameter:

The adjustment modes are the same:

For every adjustment mode, which activates dew point management, it is possible to modify the factory setting by proceeding as follows:

WARNING
When the regulation modes ‘d-EF’, ‘d-EC’ o ‘d-FP‘ are shown, the calculated dew-point (dP) value will be alternately shown.

Dew point control limitations

For further details regarding the parameters involved in the control of the dew point, see the following paragraphs.

d-EF’ Dew point control with an external probe on underfloor plants.
When the dew point regulation is active with the ‘C-dP’ parameter set on ‘d-EF’, the regulator will control both systems attached for the cooling and de-humidification according to the comparison between the dew-point temperature and the temperature measured by the external sensor, thus applying the settings of the regulation ‘d-EF’ regulation.

The following graphics describe the dew point control mode.ESBE- TPH114- Digital- Room-Thermostats-fig- (28)

Where:

When the dew point regulation is active with the ‘C-dP’ parameter set on ‘d-EC’, the regulator will control both systems attached for the cooling and de-humidification according to the comparison between the dew-point temperature and the temperature measured by the external sensor, thus applying the settings of the regulation ‘d-EC’ regulation.

The following graphics describe the dew point control modeESBE- TPH114- Digital- Room-Thermostats-fig- (29)

Dove:

If the dew point control function, ‘ C-dP ’, is activated on ‘ d-FP ’, the programmable thermo-hygrostat controls the cooling and dehumidification devices on the basis of the comparison of the temperature value of the dew point calculated and the temperature values relative to the dew points set in the sub-parameters ‘ TF1 ’ and ‘ TF2 ’.

The following graphics describe the dew point control mode
ESBE- TPH114- Digital- Room-Thermostats-fig- (30)

Dove:

On identification of the dew point temperature (table 1) which is to be respected, thresholds ‘ TF1 ’ and ‘ TF2 ’ will be set in order to obtain system adjustment such to prevent the formation of condensate.

Example:
dP > TF1 = the dehumidification system starts to operate, maintaining the cooling system active if it has already been activated.

The following situation then occurs:
dP > TF2 = The dehumidification system remains active, but the cooling system is deactivated.

Once the value of ‘ TF2 ’ is set lower than the minimum temperature of the cooling surface, this control allows to prevent the formation of condensate on the surface for any temperature and relative humidity value of the air.

ATTENTION

Generally, a minimum of 1°C is recommended for underfloor plants and 3°C for metal ceilings. ‘CndP’ Rate of check for the dew-point regulation
This parameter allows setting the minimum time, in minutes, which must elapse between two consecutive activations of the output relays, caused by the ‘ c-dP ‘ function intervention.
This time interval can be set in steps of 3 minutes; itwill be reinitialized every time the dew-point regulation mode is changed by the user (‘ d-EF ’, ‘ d-EC ’ or ‘ d-FP ‘).

‘Cntr’ THERMOSTAT RELAY ACTIVATION TIMER
Using this parameter it is possible to display the thermostat relay activation time meter relative to the actual day. The timer is automatically reset at midnight.

Proceed as follows:

‘dFLt’ SET DEFAULT DATA
With this parameter, it is possible to reset user parameters in order to bring back all the parameters to the factory defaults.

Proceed as follows:

WARNING!
Restoring the Default Data will reset all settings made by the user, such as Time Program, Heating/Cooling, Set-Points, and all other programmable data.

SWITCHING OFF – ANTIFREEZE FUNCTION

AUTOMATIC OPERATION / 24H MANUAL / PERMANENT MANUAL OVERRIDE FUNCTION

With the ‘ESBE- TPH114- Digital- Room-Thermostats-fig- (10) ‘ key, the programmable thermo-hygrostat may be forced to adjust the room temperature and humidity according to the comfort temperature and humidity set, regardless of the time programming settings. By pressing the ‘ESBE- TPH114- Digital- Room-Thermostats-fig- (10) ‘, button repeatedly you can switch from Automatic to 24-hour Manual, from 24-hour Manual to Permanent Manual, and from Permanent Manual back to Automatic. During operation in manual mode, the display does not show the time program, but only the room temperature, the status of the relays (any switch-on of the ‘ESBE- TPH114- Digital- Room-Thermostats-fig- (20) ‘ or ‘ ESBE- TPH114- Digital- Room-Thermostats-fig- (21)‘ or ‘ESBE- TPH114- Digital- Room-Thermostats-fig- (19) ‘ symbols), the ‘ 24h ‘ symbol (manual 24h) or ‘ESBE- TPH114- Digital- Room-Thermostats-fig- (10) ‘ (permanent manual) and the ‘ESBE- TPH114- Digital- Room-Thermostats-fig- (17) ‘ symbol. Pressing the ‘ESBE- TPH114- Digital- Room-Thermostats-fig- (10) ‘ button once will activate the 24-hour Manual mode and the programmable thermo-hygrostat will remain in this mode until the time 23:59 is reached, after which it will go back into the Automatic mode.

Note: If the device is set in the 24h Manual mode and the Vacation program is activated, after the Vacation period has elapsed, if it is past the time 23.59, the programmable thermo-hygrostat will go back into the Automatic mode and follow the set program schedule. Pressing the ‘ ‘ button a second time will switch the programmable thermo-hygrostat into the Permanent Manual mode and it will remain in this mode until you press the ‘ ‘ button again.

TIME/TEMPERATURE/HUMIDITY DISPLAY
By repeatedly pressing the ‘ESBE- TPH114- Digital- Room-Thermostats-fig- (8) ‘ button, the display can show the actual time with the icon relative to the temperature adjustment probe (internal ‘ ESBE- TPH114- Digital- Room-Thermostats-fig- (15)‘ or external ‘ESBE- TPH114- Digital- Room-Thermostats-fig- (16) ‘), the room temperature read by the internal sensor, distinguished by the ‘ESBE- TPH114- Digital- Room-Thermostats-fig- (15) ‘ icon, the room temperature read by the remote probe (if connected) distinguished by the ‘ESBE- TPH114- Digital- Room-Thermostats-fig- (16) ‘ icon and the room humidity read by the internal sensor, distinguished by the ‘ESBE- TPH114- Digital- Room-Thermostats-fig- (16) ‘ icon. The temperature and humidity readings are displayed and corrected by the Offset value set.

Note: If the ‘ rEG ’ parameter is set at ‘ In ’, but an error is detected on the internal sensor, the display will show ‘ SEnS E xx ’. In this situation, the adjustment will be automatically interrupted and both relays will be placed in the Normally Open position. If the ‘ rEG ’ parameter has been set at ‘ Out ‘ but the remote probe has not been connected or is damaged, the display will show the respective wording ‘ SEnS OPEN ‘ or ‘ SEnS SHrt ‘ with the ‘ESBE- TPH114- Digital- Room-Thermostats-fig- (16) ‘ icon on.

ATTENTION:

BACKLIGHTING
The display backlight turns on whenever and button is pressed. It turns off automatically 20 seconds after the last pressing of a button.

HOW TO INSERT / REPLACE BATTERIES

The battery charge status is constantly displayed by means of the ‘ESBE- TPH114- Digital- Room-Thermostats-fig- (31) ‘ symbol. The battery charge is at a maximum if all three level indicators are lit inside the symbol. If the ‘ESBE- TPH114- Digital- Room-Thermostats-fig- (32) ‘ symbol (completely empty) flashes, it means that the batteries are depleted and must be replaced. In this case, both the relays are placed in the safety position(N.C.) and the display alternately shows the time (or temperature or humidity) and the word ‘ BATT ’. If the batteries are not replaced as soon as possible, the ‘ESBE- TPH114- Digital- Room-Thermostats-fig- (20) ‘ or ‘ESBE- TPH114- Digital- Room-Thermostats-fig- (21) ‘ symbols will also flash indicating that the device is blocked.
To replace the batteries proceed as follows:

CONNECTION TO A TELEPHONE INTERFACE

IMPORTANT:

IMPORTANT
If an Off command is sent to the programmable Thermo hygrostat via the telephone interface (contact open), it is a good idea to check that the command has been executed by the programmable thermo-hygrostat by carrying out the following realignment procedure:

TECHNICAL CHARACTERISTICS

CLASSIFICATION UNDER REG. 2013.811.EC

NORMATIVE REFERENCES
The product complies with the following standards (EMC 2004/108/EC and LVD 2006/95/EC):

DIMENSIONSESBE- TPH114- Digital- Room-Thermostats-fig- (36)

WARRANTY

In view of the constant development of their products, the manufacturer reserves the right for changing technical data and features without prior notice. The consumer is guaranteed against any lack of conformity according to the European Directive 1999/44/EC as well as to the manufacturer’s document about the warranty policy. The full text of the warranty is available on request from the seller.

REFERENCE:

DOWNLOAD MANUALS:

ESBE TPH114 Digital Room Thermostats Installation Instruction

ESBEE LOGO

ESBE TPH114 Digital Room Thermostats Installation Instruction

Leave a Reply

Your email address will not be published. Required fields are marked *

To respond on your own website, enter the URL of your response which should contain a link to this post's permalink URL. Your response will then appear (possibly after moderation) on this page. Want to update or remove your response? Update or delete your post and re-enter your post's URL again. (Find out more about Webmentions.)